Standalone Programmable Controller ioPAC 5542 IEC 61131-3 Series Moxa vietnam
Features and Benefits
| Precise Data Acquisition Moxa's ioPAC 5500 RTUs offer 250 Hz-level analog input sampling rate, giving engineers the analog data precision they need to correctly analyze events. In addition, the analog input pre-recording function allows the ioPAC 5500 RTUs to continuously record analog input data before an event trigger point for improved data completeness. |
| Sustainable System Reliability The ioPAC 5500 is designed for data acquisition in all harsh environments. It can operate from -40 to 75°C (-30 to 75°C for HSPA models) with UL/cUL Class 1 Division 2. It supports EN 50121-4 for the railway industry, with rail-level surge and ESD protection. |
| Easy Data Acquisition Moxa's ioPAC 5500 RTU controllers come with Moxa's patented Active OPC server and DA-Center software. Active OPC server adds a non-polling architecture to the standard OPC protocol, giving users the advantage of push-based communication from Moxa's controllers to the SCADA systems. DA-Center, on the other hand, provides a standard OPC interface that interacts with Moxa Active OPC Server for real-time data collection. |
| Easy to Deploy Moxa's ioPAC 5500 RTU controllers are compact and come with two 10/100 Mbps Ethernet ports (two MACs, port-trunking ready), and two 3-in-1 serial ports, making the ioPAC 5500 ideal for cabinets with limited space. |
Real-Time Remote Monitoring via Cellular Technology
In this paper we discuss the technical challenges inherent in remote data acquisition, with special emphasis on applications that involve the monitoring and control of data from extremely distant pipeline, pump, and wayside equipment. We first consider what is involved in deploying a cellular communications system for remote monitoring, and the critical features and functionality required to make this a viable solution.
The following topics are covered:
Cellular Remote Monitoring Application Flyer
Moxa’s ioPAC RTU controllers are built for Remote Field Monitoring. Moxa ioPAC RTUs deliver both extreme accuracy and powerful programming tools, giving engineers a strong, efficient platform to support monitoring and analytical processes like identifying anomalous intrusions, or device failures. Designed to work reliably in harsh industrial environments, ioPAC standalone controllers feature railway-grade ESD and surge protection, wide tolerance for temperatures from -40 to 75°C (-30 to 75°C for HSPA models), and are UL/cUL Class 1 Division 2..... read more
Dimensions
• Computer | |
Main CPU | 32-bit ARM9 192 MHz CPU |
I/O CPU | 32-bit ARM Cortex M4 80 MHz CPU |
OS | Linux |
Clock | Real-time clock with battery backup |
Memory | • SDRAM: 64 MB • Flash: 32 MB • SRAM: 256 KB (battery backup lasts for 1 week) • microSD™ Slot: Up to 32 GB (SD 2.0 compatible) Note: For units operating in extreme temperatures, industrial-grade, widetemperature microSD cards are required. |
• Cellular (for the ioPAC 5542-HSPA Series) | |
Network | • Quad-band GSM/GPRS/EDGE 850/900/1800/1900 MHz • Five-band UMTS/HSPA+ 800/850/AWS/1900/2100 MHz |
Internet | HSPA: • Up to 5.76 Mbps upload speed • Up to 14.4 Mbps download speed UMTS: Up to 384 kbps upload/download speed EDGE Class 12: Up to 237 kbps upload/download speed GPRS Class 12: Up to 85.6 kbps upload/download speed |
SMS | Point-to-Point Text/PDU mode |
SIM Control Voltage | 3/1.8 V |
• Ethernet Interface | |
LAN | 2 x 10/100 Mbps, 2 MACs (IPs), RJ45 |
Protection | 1.5 kV magnetic isolation |
• Serial Interface | |
Interface | • 2 RS-232/422/485 ports, software selectable (DB9 male) • 1 RS-232 debug port (4-pin connector) |
Serial Line Protection | 15 kV ESD for all signals |
• Serial Communication Parameters | |
Parity | None, Even, Odd |
Data Bits | 7, 8 |
Stop Bits | 1, 2 |
Flow Control | RTS/CTS, XON/XOFF |
Baudrate | 300 bps to 921.6 kbps |
• Serial Signals | |
RS-232 | TxD, RxD, DTR, DSR, RTS, CTS, DCD, GND, RI |
RS-422 | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-4w | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-2w | Data+, Data-, GND |
• Inputs and Outputs | |
Digital Inputs | 8 channels |
Configurable DIOs | 8 channels |
Analog Inputs | 8 channels |
Isolation | 3k VDC or 2k Vrms |
• Digital Input | |
Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
I/O Mode | DI Counter or Frequency |
Dry Contact | • On: short to GND • Off: open |
Wet Contact | NPN (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC PNP (DI to GND): • Off: 0 to 3 VDC • On: 10 to 30 VDC |
Common Type | 4 points per COM |
Counter Frequency | 1 kHz |
Digital Filtering Time Interval | Software selectable (by 0.5 ms) |
• Digital Output | |
Type | Sink |
I/O Mode | DO or PWM |
Pulse Output Frequency | 1 kHz |
Over-Voltage Protection | 45 VDC |
Over-Current Protection | 2.6 A (4 channels @ 650 mA) |
Over-Temperature Shutdown | 175°C (typical), 150°C (min.) |
Current Rating | 200 mA per channel |
• Analog Input | |
Type | Differential Input |
Resolution | 16 bits |
I/O Mode | Voltage / Current |
Input Range | 0 to 10 VDC, -10 to 10 VDC, 0 to 20 mA, 4 to 20 mA (wire off) |
Historical Data Buffering | 60 KB per channel, 120-second data buffer at 250 Hz |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Sampling Rate | • All channels: 2000 samples/sec • Per channel: 250 samples/sec |
Input Impedance | 2 mega-ohms (min.) |
Built-in Resistor for Current Input | 120 ohms (min.) |
• Software Characteristics | |
Automation Languages | C/C++ or IEC 61131-3 |
Protocols | Modbus TCP/RTU (master/slave), SNMP TCP/IP, UDP, DHCP, BOOTP, SNTP, SMTP |
• Power Requirements | |
Input Voltage | 24 VDC (9 to 48 VDC) |
Input Current | • ioPAC 5542-HSPA series: 305 mA @ 24 VDC • ioPAC 5542 series: 264 mA @ 24 VDC |
• Physical Characteristics | |
Housing | Aluminum |
Dimensions | 90.05 x 135 x 105.4 mm (3.55 x 5.32 x 4.15 in) |
Weight | • ioPAC 5542-HSPA Series: 1100 g (2.43 lb) • ioPAC 5542 Series: 1000 g (2.20 lb) |
Mounting | DIN rail (standard), wall (optional) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | • ioPAC 5542 Series: -40 to 75°C (-40 to 176°F) • ioPAC 5542-HSPA Series: -30 to 75°C (-22 to 176°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
Altitude | 2000 m Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
• Standards and Certifications | |
Safety | UL 508 |
EMC | EN 55022/24 |
EMI | FCC Part 15 Subpart B Class A, CISPR 22 |
EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1000 MHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L); Signal: 1 kV IEC 61000-4-6 CS: 3 V IEC 61000-4-8 PFMF: 1 A/m |
Radio | NCC |
Rail Traffic | EN 50121-4 |
Hazardous Location | Class 1 Division 2 Note: Please check Moxa’s website for the most up-to-date certification status. |
• Warranty | |
Warranty Period | 5 years |
Details | www.anhnghison.com |