Fieldbus Gateways MGate 4101-MB-PBS Series Moxa vietnam
Features and Benefits
- Protocol conversion between Modbus and PROFIBUS
- Windows utilities with innovative QuickLink function for automatic configuration within minutes
- Redundant dual DC power inputs and relay output supported
- Embedded data packet analyzer
- Powerful and visual diagnostic tool
- -40 to 75°C wide operating temperature models available
Overview
The MGate 4101-MB-PBS gateway provides a communication portal between PROFIBUS PLCs (e.g. Siemens S7-400 and S7-300 PLCs) and Modbus devices. With the QuickLink feature, I/O mapping can be accomplished within a matter of minutes. All models are protected with a rugged metallic casing, are DIN-rail mountable, and offer optional built-in optical isolation.
QuickLink and Windows Utilities for Easy Setup and Traffic Monitoring
The QuickLink windows utility uses a serial console port to connect to the MGate 4101-MB-PBS and makes configuration and operation as easy as possible. QuickLink can finish the configuration in just a few minutes by passively detecting Modbus requests with the AutoLearning function, and performing error-free I/O mapping with the AutoMapping feature. QuickLink drastically reduces Modbus-to-PROFIBUS integration time when compared to conventional I/O mapping, which can easily require days to complete. Additionally, embedded monitoring tools can maintain logs of Modbus communication packets and assist in troubleshooting.
Redundant Power Inputs
The MGate 4101-MB-PBS has dual power inputs for greater reliability. The power inputs allow simultaneous connections to two live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus-to-PROFIBUS gateways ideal for demanding industrial applications.
Warning by Relay Output
A relay output is provided for the power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance.
Dimensions
• PROFIBUS Interface | |
Protocol | PROFIBUS DP-V0 Slave |
Number of Ports | 1 |
Data Rate | 9600 bps to 12 Mbps |
Connector | DB9 female |
Isolation | 2 kV (built-in) |
DIP Switch | For termination |
Rotary Switch | PROFIBUS address 0-99 (address 100-125 supported through software configuration) |
• Modbus Interface | |
Protocol | Modbus RTU/ASCII Master/Slave |
Number of Ports | 1 |
Serial Standards | RS-232/422/485, software selectable |
Connectors | DB9 male |
ESD Protection | 15 kV for all signals |
RS-485 Data Direction Control | ADDC® (automatic data direction control) |
Pull High/Low Resistor for RS-485 | 1 kΩ, 150 kΩ |
Terminator for RS-485 | 120 Ω |
Data Bits | 7, 8 |
Stop Bits | 1, 2 |
Parity | None, Even, Odd, Space, Mark |
Flow Control | RTS/CTS, DTR/DSR (RS-232 only) |
Baudrate | 50 bps to 921.6 kbps |
• Serial Signals | |
RS-232 | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
RS-422 | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-4w | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-2w | Data+, Data-, GND |
• Software | |
Configuration Options | Serial Console, Windows Utility |
Utility | MGate Manager for Windows 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2 |
Support | QuickLink, Paging |
• Physical Characteristics | |
Housing | Metal, IP30 |
Weight | 500 g (1.10 lb) |
Dimensions | 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in) |
• Environmental Limits | |
Operating Temperature | Standard Models: 0 to 60°C (32 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Vibration | IEC 60068-2-6, IEC 60068-2-64 |
Shock | IEC 60068-2-27 |
Drop | IEC 60068-2-32 |
• Power Requirements | |
Input Voltage | 12 to 48 VDC |
Input Current | MGate 4101-MB-PBS: 340 mA @ 12 VDC; 130 mA @ 48 VDC MGate 4101I-MB-PBS: 375 mA @ 12 VDC; 140 mA @ 48 VDC |
Power Connector | Terminal block |
• Standards and Certifications | |
Safety | UL 60950-1, EN 60950-1 |
Hazardous Location | Class 1 Division 2, ATEX, IECEx |
EMC | EN 55032/24 |
EMI | CISPR 32, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 3 V/m IEC 61000-4-8 PFMF |
• MTBF (mean time between failures) | |
Time | 513,139 hrs |
Standard | Telcordia SR332 |
• Warranty | |
Warranty Period | 5 years |
Details | www.anhnghison.com |