Smart Wireless I/O ioLogik W5340-HSPA Moxa vietnam
Features and Benefits
- Front-end intelligence with patented Click&Go control logic, up to 24 rules
- Using Active OPC Server software, SCADA systems can directly communicate with cellular devices hidden behind private IP addresses
- Active communication with Active OPC Server
- Automatically complement disconnection period data with DA-Center software
- Daisy chain up to 3 ioLogik E1200 units
- 3-in-1 RS-232/422/485 serial port for connecting to serial devices in the field
- Supports SNMPv1/v2c
- Simplify I/O management with MXIO library for Windows or Linux platforms
- Wide operating temperature range of -30 to 70°C (-22 to 158°F)
Introduction
The ioLogik W5340-HSPA micro RTU controller is a rugged, compact solution for remote monitoring and alarm systems. With the ioLogik W5340-HSPA, you can define a cellular connection strategy, including Always-On and Wake-On-Demand, to optimize data transmission rates for different applications. In addition, the operational cost of cellular communication depends on the data transmission rate. With Moxa’s active technology, you can expect to cut transmission costs in half and offer different cellular connection strategies to achieve better data transmission fees.
Automatic Data Updates from SD Cards Following Network Failures
When Active OPC Server™ and DA-Center™ are used together, upon network reconnection Moxa’s ioLogik W5300 series of RTU controllers are able to transmit data logs collected offline. After each network connection, the DA-Center database gateway will compare historical data stored on the ioLogik W5300’s local SD card with its received, real-time data, and then supplement any missing data by requesting re-transmission from the RTU.
Dynamic IP Assignments
For most cellular solutions, each remote modem as well as the central SCADA server is assigned static public IP when establishing bi-directional communication. Yet cellular network carriers charge higher monthly fees for static, public IPs than dynamic, private ones. Moxa’s ioLogik W5300 series and patented Active OPC Server allow users to implement dynamic IP assignments for the RTUs. The ioLogik W5300 can automatically establish communications with the Active OPC Server using a fixed IP, and the Active OPC Server™ will receive and register the ioLogik W5300’s IP address and receive or record tag updates accordingly.
I/O Expandability
The ioLogik W5300 can integrate external wired clients via daisychained ioLogik E1200 I/O modules. ioLogik E1200 modules support simple daisy chaining and cost-free peer-to-peer I/O extensions. Through the RJ45 Ethernet port, the ioLogik W5300 can support up to three connected ioLogik E1200 series I/O modules to enforce a flexible and scalable network expansion that best fits customers’ needs.
This rugged, compact solution is suitable for the following applications.
- Water and wastewater industries
- Broadcast and telecom radio tower monitoring
- Infrastructure management
- Oil & gas, power, and transportation
- Lighting control monitoring
Towards a Smarter World with Moxa’s I/O Solutions
Smart I/O Success Stories
The innovation of Moxa’s data acquisition engineers is reflected in Moxa’s latest I/O products, which are helping companies around the world simplify the management of distributed control systems, and as a result reduce costs and create business growth. In addition, Moxa also provides innovative data acquisition software that helps businesses simplify the process of integrating I/O devices with an existing network. This smart automation software not only helps users gather data faster and more efficiently, but also helps businesses identify, assess, and monitor potential risks.
Download this 16-page Smart I/O Brochure to learn more about:
- The Smarter World Trend
- Moxa’s Innovative Designs
- Moxa’s Easy-to-Use Automation Software
- Success Stories Based on Moxa’s Smart I/O Solutions
- Moxa’s Smart IO Product Selection Guide
Related White Papers
A New Chapter in the Legacy of RS-485 Data Acquisition Devices
This white paper provides insight into the future of RS-485 data acquisition devices, and how Moxa is adding a new chapter to the legacy of RS-485 data acquisition devices.
SNMP I/O Devices Make Monitoring Environmental Conditions Easy
This paper will first explain what SNMP is, why you should use SNMP for environmental monitoring, and then discuss how an SNMP environmental monitoring device will help ease the management and implementation process.
Hardware Informations:
Dimensions (unit = mm)
• LAN | |
Ethernet | 1 10/100 Mbps RJ45 port, with up to 3 ioLogik E1200 units daisy-chained |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, SNMP, SNTP |
• Serial | |
Interface | 1 RS-232/422/485 (software selectable) DB9 male or terminal block port |
Parity | None, Odd, Even, Space, Mark |
Data Bits | 5, 6, 7, 8 |
Stop Bits | 1, 2 |
Flow Control | None, Hardware, XON/XOFF |
Baudrate | 300 to 115200 bps |
Protocols | Modbus/RTU (master/gateway), serial tunnel mode (client/server) |
• Inputs and Outputs | |
Configurable DIOs (by software) | 8 channels |
Relays | 2 channels |
Analog Inputs | 4 channels |
Isolation | 3k VDC or 2k Vrms |
• Digital Input | |
Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
I/O Mode | DI or Event Counter |
Dry Contact | • On: short to GND • Off: open |
Wet Contact (DI to GND) | • On: 0 to 3 VDC • Off: 10 to 30 VDC |
Common Type | 4 points per COM |
Counter Frequency | 900 Hz |
Digital Filtering Time Interval | Software configurable |
• Digital Output | |
Type | Sink |
I/O Mode | DO or Pulse Output |
Pulse Output Frequency | 1 kHz |
Over-Voltage Protection | 45 VDC |
Over-Current Protection | 2.6 A (4 channels @ 650 mA) |
Over-Temperature Shutdown | 160°C (min.) |
Current Rating | 200 mA per channel |
DIO Output Leakage Current | 3.6 mA @ 24 VDC |
• Relay | |
Type | Form A (N.O.) power relay |
Contact Current Rating | Resistive Load: 1 A @ 30 VDC, 250 VAC, 110 VAC |
Initial Insulation Resistance | 1000 micro-ohms (min.) @ 500 VDC |
Mechanical Endurance | 5,000,000 operations |
Electrical Endurance | 600,000 operations @ 1 A resistive load |
Contact Resistance | 100 milli-ohms (max.) |
Pulse Output | 0.3 Hz at rated load |
Note: Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik W5340-HSPA may malfunction when operating in high condensation environments below 0° Celsius. | |
• Analog Input | |
Type | Differential input |
Resolution | 16 bits |
I/O Mode | Voltage / Current (software selectable) |
Input Range | 0 to 10 V, ±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA |
Accuracy | • ±0.1% FSR @ 25°C • ±0.3% FSR @ -30 and 70°C |
Sampling Rate | All channels: 32 samples/sec Per channel: 8 samples/sec Single channel: 100 samples/sec |
Input Impedance | 200k ohms (min.) |
Built-in Resistor for Current Input | 120 ohms |
• Power Requirements | |
Input Voltage | 12 to 36 VDC |
Input Current | 196 mA @ 24 VDC |
• Physical Characteristics | |
Wiring | I/O cable, 14 AWG (max.) |
Dimensions | 46.8 x 135 x 105 mm (1.84 x 5.31 x 4.13 in) |
Weight | 495 g (1.09 lb) |
Mounting | DIN rail (standard), wall (optional) |
• Storage | |
Expansion Slot | Up to 32 GB SD™ memory card (SD 2.0 compatible) |
Note: For units operating in extreme temperatures, industrial-grade, wide temperature SD cards are required. | |
• Environmental Limits | |
Operating Temperature | Standard Models: -10 to 55°C (14 to 131°F) Wide Temp. Models: -30 to 70°C (-22 to 158°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
Altitude | Up to 2000 m |
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes. | |
• Standards and Certifications | |
Safety | UL 508, EN 60950-1 |
EMC | EN 55032/24 |
EMI | CISPR 32, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV IEC 61000-4-6 CS: Signal: 3 V/m IEC 61000-4-8 Magnetic Field: 1 A/m |
Radio | R&TTE: EN 301 489-1, EN 301 489-7, EN 301 489-24, EN 301 511, EN 301 908-1; NCC |
Green Product | RoHS, CRoHS, WEEE |
Note | Please check Moxa’s website for the most up-to-date certification status. |
• MTBF (mean time between failures) | |
Time | 280,739 hrs |
Standard | Telcordia SR332 |
• Warranty | |
Warranty Period | 2 years* |
Details | www.anhnghison.com |
*Because of the limited lifetime of power relays, products that use that component are covered by a 2-year warranty. |