I-O-Module-ioPAC-8020-Series-Expansion-Modules-Moxa-vietnam.jpg

I/O Module ioPAC 8020 Series Expansion Modules Moxa vietnam


Features and Benefits

  • RM-1050-T: 10 channel-to-channel isolated DIs, 110 VDC, sink/source type
  • RM-1602-T: 16 digital inputs, 24 VDC, sink/source type
  • RM-2600-T: 16 digital outputs, 24 VDC, sink-type
  • RM-3802-T: 8 analog inputs, 4 to 20 mA
  • RM-3810-T: 8 analog inputs, 0 to 10 V
  • KM-2430-T: 4-port unmanaged Ethernet switch module

Fast Track Integration for Wayside Condition Monitoring and Preventive Maintenace

This white paper will discuss how railway operators are adopting increasingly sophisticated condition-based maintenance regimes to control costs and improve track performance, some of the key difficulties system integrators need to overcome when deploying wayside condition monitoring systems for railway preventive maintenance, and how using a single condition monitoring platform can save time and costs for deployment and maintenance.

 

Railway Preventive Maintenance Solutions Flyer

 

See how Moxa's ioPAC 8500 RTU controllers make railway preventive maintenance easy. The RTUs provide extremely accurate data, giving engineers the information they need to identify anomalous conditions, before failures occur. The ioPAC 8500 RTUs are also designed to work reliably in harsh environments, and modules can be easily replaced to shorten system downtime.

 

RM-1602-T Specifications
Digital Inputs 16 channels, 24 VDC, sink/source type
On 10 to 30 VDC
Off 0 to 3 VDC
Input Impedance 3 kilo-ohms (typical)
Common Type 8 points per 2 COMs
Response Time 10 ms
Isolation 3k VDC or 2k Vrms
Operating Temperature -40 to 75°C (-40 to 176°F)
Input Current 7 mA @ 24 VDC
Wiring I/O cable, 14 AWG (max.)
MTBF 4,132,863 hrs (Standard: Telcordia SR332)
 
RM-1050-T Specifications
Digital Inputs 10 channels, 110 VDC, channel-to-channel isolation
On 50 to 175 VDC
Off 0 to 15 VDC
Input Impedance 120 kilo-ohms (typical)
Response Time 10 ms
Isolation 3k VDC or 2k Vrms
Channel-to-Channel Isolation 2.5k VDC
Operating Temperature -40 to 75°C (-40 to 176°F)
Input Current 7 mA @ 24 VDC
Wiring I/O cable, 14 AWG (max.)
MTBF 3,993,435 hrs (Standard: Telcordia SR332)
 
RM-2600-T Specifications
Digital Outputs 16 channels, 24 VDC, sink-type
Output Impedance 120 milli-ohms (typical)
Current Rating 200 mA per channel
Off-state Resistance 500 kilo-ohms (typical)
Response Time 10 ms
Over Current Protection 2.6 A (4 channels @ 650 mA)
Isolation 3k VDC or 2k Vrms
Operating Temperature -40 to 75°C (-40 to 176°F)
Input Current 10 mA @ 24 VDC
Wiring I/O cable, 14 AWG (max.)
MTBF 4,440,241 hrs (Standard: Telcordia SR332)
 
RM-3802-T Specifications
Analog Inputs 8 channels, differential
Input Range 4 to 20 mA
Input Impendence 120 ohms
Resolution 16 bits, 0.24 μA/bit
Accuracy ±0.1%, FSR @ 25°C
±0.3%, FSR @ -40°C and 75°C
Sampling Rate • All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
Isolation 3k VDC or 2k Vrms
Operating Temperature -40 to 75°C (-40 to 176°F)
Input Current 78 mA @ 24 VDC
Wiring I/O cable, 14 AWG (max.)
MTBF 1,222,361 hrs (Standard: Telcordia SR332)
 
RM-3810-T Specifications
Analog Inputs 8 channels, differential
Input Range 0 to 10 VDC
Input Impendence 10 mega-ohms (min.)
Resolution 16 bits, 0.15 μA/bit
Data Format 16-bit integer (2’s complement)
Accuracy ±0.1%, FSR @ 25°C
±0.3%, FSR @ -40°C, 75°C
Sampling Rate • All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
Isolation 3k VDC or 2k Vrms
Operating Temperature -40 to 75°C (-40 to 176°F)
Input Current 78 mA @ 24 VDC
Wiring I/O cable, 14 AWG (max.)
MTBF 1,225,957 hrs (Standard: Telcordia SR332)
 
KM-2430-T Specifications
Standards IEEE 802.3 for 10BaseT
IEEE 802.3u for 100BaseT(X)
IEEE 802.3x for Flow Control
Processing Type Store and Forward
Interface Front cabling, M12 connector, 10/100BaseT(X) auto negotiation speed
Operating Temperature -40 to 75°C (-40 to 176°F)
Input Current 20 mA @ 24 VDC
MTBF 3,873,592 hrs (Standard: Telcordia SR332)
 
Common Specifications
Power Requirements
Input Voltage 12 to 36 VDC
Environmental Limits
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
Standards and Certifications
Safety UL 508
EMC EN 55032, EN 55024
EMI FCC Part 15 Subpart B Class A, CISPR 32, CISPR 16-1-2, 16-2-1, 16-2-3, EN 61000-6-4
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS:
   80 MHz to 1000 MHz: 10 V/m
   1400 MHz to 2100 MHz: 3 V/m
   2100 MHz to 2700 MHz: 1 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L); Signal: 1 kV (9-slot version)
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF: 30 A/m
Rail Traffic EN 50155*, EN 50121-3-2, EN 50121-4. Complies with a portion of EN 50155 specifications. Please contact Moxa or a Moxa distributor for details.
*Complies with a portion of EN 50155 specifications.
Warranty
Warranty Period 5 years
Details www.anhnghison.com