I/O Module ioPAC 8500 Series Expansion Modules Moxa vietnam
Features and Benefits
- 85M-1602-T: 16 digital inputs, 24 VDC, sink/source type
- 85M-2600-T: 16 digital outputs, 24 VDC, sink-type
- 85M-3800-T: 8 analog inputs, 4 to 20 mA
- 85M-3810-T: 8 analog inputs, 0 to 10 VDC
- 85M-3801-T: 8 analog inputs, 4 to 20 mA, 40 kHz
- 85M-3811-T: 8 analog inputs, 0 to 10 VDC, 40 kHz
- 85M-5401-T: 4 serial ports (RS-232/422/485)
- 85M-6600-T: 6 RTDs
Introduction
Fast Track Integration for Wayside Condition Monitoring and Preventive Maintenace
This white paper will discuss how railway operators are adopting increasingly sophisticated condition-based maintenance regimes to control costs and improve track performance, some of the key difficulties system integrators need to overcome when deploying wayside condition monitoring systems for railway preventive maintenance, and how using a single condition monitoring platform can save time and costs for deployment and maintenance.
Railway Preventive Maintenance Solutions Flyer
See how Moxa's ioPAC 8500 RTU controllers make railway preventive maintenance easy. The RTUs provide extremely accurate data, giving engineers the information they need to identify anomalous conditions, before failures occur. The ioPAC 8500 RTUs are also designed to work reliably in harsh environments, and modules can be easily replaced to shorten system downtime.
85M-1602-T Specifications | |
• Inputs and Outputs | |
Digital Inputs | 16 channels |
Isolation | 3k VDC or 2k Vrms |
• Digital Input | |
Sensor Type | Wet contact (NPN or PNP), dry contact |
I/O Mode | DI, Counter or Frequncy |
Dry Contact | • On: short to GND • Off: open |
Wet Contact (DI to COM) | • Off: 0 to 3 VDC • On: 10 to 30 VDC |
Common Type | 8 points per COM |
Counter Frequency | 5 kHz |
Digital Filtering Time Interval | Software selectable (by 0.1 ms) |
• Physical Characteristics | |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 363.6 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 1,132,561 hrs |
Standard | Telcordia SR332 |
85M-2600-T Specifications | |
• Inputs and Outputs | |
Digital Outputs | 16 channels |
Isolation | 3k VDC or 2k Vrms |
• Digital Output | |
Type | Sink |
I/O Mode | DO or PWM |
Pulse Output Frequency | 5 kHz |
Over-Voltage Protection | 45 VDC |
Over-Current Protection | 2.6 A (4 channels @ 650 mA) |
Over-Temperature Shutdown | 175°C (typical), 150°C (min.) |
Current Rating | 200 mA per channel |
• Physical Characteristics | |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 257.6 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 792,571 hrs |
Standard | Telcordia SR332 |
85M-3800-T Specifications | |
• Inputs and Outputs | |
Analog Inputs | 8 channels |
Isolation | 3k VDC or 2k Vrms |
• Analog Input | |
Type | Differential |
Resolution | 16 bits |
I/O Mode | 4 to 20 mA (wire off) |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Sampling Rate | • All channels: 100 samples/sec • Per channel: 12.5 samples/sec |
Input Impedance | 125 ohms (min.) |
• Physical Characteristics | |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 318.2 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 1,512,906 hrs |
Standard | Telcordia SR332 |
85M-3810-T Specifications | |
• Inputs and Outputs | |
Analog Inputs | 8 channels |
Isolation | 3k VDC or 2k Vrms |
• Analog Inputs | |
Type | Differential |
Resolution | 16 bits |
I/O Mode | 0 to 10 VDC |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Sampling Rate | • All channels: 100 samples/sec • Per channel: 12.5 samples/sec |
Input Impedance | 200 kilo-ohms (min.) |
• Physical Characteristics | |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 315.2 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 1,530,690 hrs |
Standard | Telcordia SR332 |
85M-3801-T Specifications | |
• Inputs and Outputs | |
Analog Inputs | 8 channels |
Isolation | 3k VDC or 2k Vrms |
• Analog Input | |
Type | Differential |
Resolution | 16 bits |
I/O Mode | 4 to 20 mA (wire off) |
Historical Data Buffering | 60 KB per channel, 6-second data buffer at 5 kHz |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Sampling Rate | • All channels: 40k samples/sec • Per channel: 5k samples/sec |
Input Impedance | 125 ohms (min.) |
• Physical Characteristics | |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 378.8 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 1,426,112 hrs |
Standard | Telcordia SR332 |
85M-3811-T Specifications | |
• Inputs and Outputs | |
Analog Inputs | 8 channels |
Isolation | 3k VDC or 2k Vrms |
• Analog Inputs | |
Type | Differential |
Resolution | 16 bits |
I/O Mode | 0 to 10 VDC |
Historical Data Buffering | 60 KB per channel, 6-second data buffer at 5 kHz |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Sampling Rate | • All channels: 40k samples/sec • Per channel: 5k samples/sec |
Input Impedance | 20 mega-ohms (min.) |
• Physical Characteristics | |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 378.8 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 1,426,112 hrs |
Standard | Telcordia SR332 |
85M-6600-T Specifications | |
• Inputs and Outputs | |
RTD Inputs | 6 channels |
Isolation | 3k VDC or 2k Vrms |
• RTDs | |
Input Type | • PT50, PT100, PT200, PT500 (-200 to 850°C) • PT1000 (-200 to 350°C) • JPT100, JPT200, JPT500 (-200 to 640°C) • JPT1000 (-200 to 350°C) • NI100, NI200, NI500 (-60 to 250°C) • NI1000 (-60 to 150°C) • NI120 (-80 to 260°C) • Resistance of 310, 620 |
Sampling Rate (single channel) | • All channels: 12 samples/sec • Per channel: 2 samples/sec |
Resolution | 0.1°C or 0.1 ohms |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Input Impedance | 625 kilo-ohms (min.) |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 201.5 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 571,446 hrs |
Standard | Telcordia SR332 |
85M-6810-T Specifications | |
• Inputs and Outputs | |
Analog Inputs | 8 channels |
Isolation | 3k VDC or 2k Vrms |
• Thermocouples | |
Sensor Type | J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C) |
Millivolt Type | • Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV • Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on) |
Sampling Rate (single channel) | • All channels: 12 samples/sec • Per channel: 1.5 samples/sec |
Resolution | 16 bits |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Input Impedance | 1 mega-ohm (min.) |
Wiring | I/O cable, 16 AWG (max.) |
Connector | Spring-type terminal block |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 175.5 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 2,324,891 hrs |
Standard | Telcordia SR332 |
85M-5401-T Specifications | |
• Serial Communication | |
Interface | 4 RS-232/422/485 ports, software selectable (DB44 female) |
Isolation | 3k VDC or 2k Vrms Note: DB44 to 4-port DB9 cable included in the package. |
• Serial Communication Parameters | |
Parity | None, Even, Odd |
Data Bits | 7, 8 |
Stop Bits | 1, 2 |
Flow Control | RTS/CTS, XON/XOFF |
Baudrate | 300 bps to 921.6 kbps |
• Serial Signals | |
RS-232 | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
RS-422 | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-4w | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-2w | Data+, Data-, GND |
• Physical Characteristics | |
Connector | DB44 female |
• Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 176°F) |
• Power Requirements | |
Input Current | 375.8 mA @ 3.3 VDC |
• MTBF (mean time between failures) | |
Time | 596,611 hrs |
Standard | Telcordia SR332 |
Common Specifications | |
• Power Requirements | |
Input Voltage | 24 VDC (9 to 48 VDC) |
• Environmental Limits | |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
• Standards and Certifications | |
Safety | UL 508 |
EMC | EN 55032/24 |
EMI | FCC Part 15 Subpart B Class A, CISPR 32 |
EMS | IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1000 MHz: 3 V/m 1400 MHz to 2100 MHz: 3 V/m 2100 MHz to 2700 MHz: 1 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L); |
Rail Traffic | EN 50155*, EN 50121-3-2, EN 50121-4 *Complies with a portion of EN 50155 specifications. |
• Warranty | |
Warranty Period | 5 years |
Details | www.anhnghison.com |