IEC 61850-3 PT-G503-PHR-PTP Series Moxa vietnam
Features
- IEC 61850-3, IEEE 1613 (power substations) compliant
- IEC 62439-3 Clause 4 (PRP) and Clause 5 (HSR) compliant
- PRP/HSR Coupling and QuadBox functions supported
- Ethernet console reserved for local access
- Built-in MMS server, based on IEC 61850-90-4 switch modeling for power SCADA
- Hardware-based IEEE 1588v2 PTP supported
- Design ready for NERC CIP compliance system development
- Isolated redundant power inputs with universal 24/48 VDC or 110/220 VDC/VAC power supply range
- -40 to 85°C operating temperature range
Introduction
The PT-G503-PHR-PTP series redundancy boxes (RedBoxes) are compliant with the latest standardized redundancy protocols for industrial automation networks, IEC 62439-3 Clause 4 (Parallel Redundancy Protocol, PRP) and IEC 62439-3 Clause 5 (High-availability Seamless Redundancy, HSR). PRP/HSR ensures the highest system availability and data integrity for mission-critical applications in electrical substation and/or process automation systems that require zero recovery time redundancy. The redundant protocols Coupling and QuadBox are also supported. With Coupling and QuadBox, HSR rings can be connected to make the redundant network more versatile. The PT-G503-PHR-PTP series comes with three 10/100/1000BaseT(X) and 100/1000BaseSFP slot combo ports.
One slot (INTERLINK port) is for an internal link for connecting with a SAN (Singly Attached Node). The other two ports (LAN A and LAN B ports) are for PRP/HSR redundant protocol communications. With this full Gigabit Ethernet port design, the PT-G503-PHR-PTP series provides high performance for PRP/HSR systems.
The PT-G503-PHR-PTP series also provides hardware-based IEEE 1588v2 PTP when in end-to-end one-step transparent clock mode for timing-critical applications and isolated redundant power inputs with 24/48 VDC or 110/220 VDC/VAC power supply ranges to increase the reliability of the power supply.
White Paper
Enabling Efficient and Visually Represented PRP/HSR Network Management
Creating a network management interface of devices and systems using different protocols can create risks and management issues that compromise effectiveness and security for substation automation networks. An efficient and visually represented PRP/HSR network using power SCADA with specially designed management middleware can effectively avoid these problems........more
Brochure
IEC 61850 Substation Solutions
Maximizing a power substation’s availability and safety is the ultimate goal for both transmission grid operators and SAS (Substation Automation System) integrators. A properly optimized SAS ensures safe and continuous operation of substations. This brochure examines some key application scenarios that involve availability and safety, and considers the practical concerns electricity suppliers must account for when planning substation upgrades. In each case the focus is on how Moxa’s communication and computing solutions best minimize error probability, detect errors faster, and speed up fault corrections within the context of IEC 61850.......more
• Technology | |
Standards | IEEE 802.3 for 10BaseT IEEE 802.3u for 100BaseT(X) and 100BaseFX IEEE 802.3ab for 1000BaseT(X) IEEE 802.3z for 1000BaseX |
• Software Features | |
Management | IPv4/IPv6, PRP/HSR, SNMPv1/v2c/v3, DHCP Client, BootP, SMTP, RARP, HTTP, Telnet, LLDP, Flow Control, Back Pressure Flow Control, SNMP Inform, Port Mirror, Fiber Check, Syslog, RMON |
Filter | Multicast Filter Behavior |
Redundancy Protocols | PRP/HSR, RSTP Transparent |
Security | RADIUS, TACACS+, Trusted Access Control, Authentication Certificate (SSL Certificate, SSH Key Regenerate) |
Time Management | SNTP, NTP Server/Client, IEEE 1588v2 PTP |
Industrial Protocols | Modbus/TCP |
MIB | IEC 62439-3 MIB |
Power Substation | MMS |
• Interface | |
Gigabit Ethernet | 3 x 10/100/1000BaseT(X) ports or 100/1000BaseSFP combo ports |
Console Port | Ethernet console (10/100/1000 Mbps RJ45), USB-serial console (Type B connector) |
Storage Port | USB storage (Type A connector for ABC-02-USB) |
Alarm Contact | 1 relay output with current carrying capacity of 1 A @ 24 VDC |
Digital Inputs | 1 input with the same ground, but electrically isolated from the electronics• +13 to +30 V for state “1” • -30 to +3 V for state “0” • Max. input current: 8 mA |
• Power Requirements | |
Input Voltage | • WV: 24/48 VDC • HV: 110/220 VDC/VAC |
Operating Voltage | • WV: 18 to 72 VDC • HV: 88 to 300 VDC, 85 to 264 VAC |
Input Current | • Max. 0.660/0.360 A @ 24/48 VDC • Max. 0.150/0.080 A @ 110/220 VDC • Max. 0.260/0.170 A @ 110/220 VAC |
Overload Current Protection | Present |
Connection | 5-pin terminal block |
Reverse Polarity Protection | Present |
• Physical Characteristics | |
Housing | Aluminum alloy |
IP Rating | IP40 protection |
Dimensions | 80 x 160 x 110 mm (3.15 x 6.30 x 4.33 in) |
Weight | 1210 g (2.69 lb) |
Installation | DIN-rail mounting |
• Environmental Limits | |
Operating Temperature | -40 to 85°C (-40 to 185°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
• Standards and Certifications | |
High Availability Automation Networks | IEC 62439-3 |
Safety | UL 508 |
EMI | FCC Part 15 Subpart B Class A, EN 55032 Class A |
EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 35 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 IEC 61000-4-11 |
Electrical Substation | IEC 61850-3, IEEE 1613 |
Rail Traffic | EN 50121-4 |
• MTBF (mean time between failures) | |
Time | PT-G503-PHR-PTP-WV:440,857 hrs PT-G503-PHR-PTP-HV:566,844 hrs |
Standard | Telcordia TR/SR |
• Warranty | |
Warranty Period | 5 years |
Details | www.anhnghison.com |