Ethernet I/O ioLogik E1510-T Moxa vietnam
- User-definable Modbus/TCP Slave addressing
- Active communications with MX-AOPC UA Server
- Easy mass deployment and configuration with ioSearch utility
- Friendly configuration via web browser
- Simplify I/O management with MXIO library on either Windows or Linux platform
- EN 50121-3-2, EN 50121-4, and EN 50155* approval for harsh railway environments
- Wide operating temperature range: -40 to 85°C (-40 to 185°F)
*Complies with a portion of EN 50155 specifications
Introduction
The ioLogik E1510 Ethernet Remote I/O product has a ruggedized aluminum housing, and is compliant with EN 50121-3-2, EN 50121-4 and essential sections of EN 50155 standard, both of which are essential for electronic equipment used in rolling stock applications. This rugged platform features a wide operating temperature range of -40 to 85°C to deliver consistent performance in harsh environment.
DI Channel Isolation Protection
Channel to channel isolation provides the most robust protection against electrical surges. With this topology, each DI channel on the ioLogik E1510 is individually isolated to ensure highly stable data communication. In cases of high surge events such as lighting strikes, the device is protected from current surge by this channel isolation feature. This is a critical requirement in railway applications when considering an Ethernet-based I/O solution.
Seamless SCADA Connectivity with Active OPC Technology
Moxa’s patented Active OPC Server is a software package that operates as an OPC driver for HMI and SCADA systems . The Active OPC server enables the ioLogik E1510 to actively communicate with the SCADA system to provide instant I/O status.
ioLogik E1510-T Specifications | |
• Inputs and Outputs | |
Digital Inputs | 12 channels (channel-to-channel isolation) |
Isolation | 3k VDC or 2k Vrms |
• Digital Input | |
Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
I/O Mode | DI or Event Counter |
Dry Contact | • On: short to GND • Off: open |
Wet Contact (DI to GND) | • On: 0 to 3 VDC • Off: 10 to 30 VDC |
Counter Frequency | 250 Hz |
Digital Filtering Time Interval | Software configurable |
• MTBF (mean time between failures) | |
Time | 507,064 hrs |
Standard | Telcordia SR332 |
Common Specifications | |
• LAN | |
Ethernet | 1 10/100 Mbps, M12 |
Protection | 1.5 kV magnetic isolation |
Protocols | Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, HTTP |
• Power Requirements | |
Input Voltage | 12 to 48 VDC |
Input Current | 150 mA @ 24 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 144 x 124 x 30 mm (5.67 x 4.88 x 1.18 in) |
Weight | Under 825 g (1.82 lb) |
Mounting | DIN-rail (standard), wall (with optional kit) |
• Environmental Limits | |
Operating Temperature | -40 to 85°C (-40 to 185°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
Altitude | Up to 2000 m |
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes. | |
Conformal Coating | Applies only to -CT models |
• Standards and Certifications | |
Safety | UL 508 |
EMC | EN 61000-6-2/6-4 |
EMI | FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m 1.4 GHz to 2 GHz: 3 V/m 2 GHz to 2.7 GHz: 1 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: |
Rail Traffic | EN 50155*, EN 50121-4 |
*Complies with a portion of EN 50155 specifications. | |
Green Product | RoHS, CRoHS, WEEE |
Note: Please check Moxa’s website for the most up-to-date certification status. | |
• Warranty | |
Warranty Period | 5 years |
Details | www.anhnghison.com |