IEC 61850-3 PT-508 Series Moxa vietnam
Features and Benefits
- IEC 61850-3 and IEEE 1613 (power substations) compliant
- Turbo Ring and Turbo Chain (recovery time < 20 ms @ 250 switches), RSTP/STP, and MSTP for network redundancy
- Easy network management by web browser, CLI, Telnet/serial console, windows utility, and ABC-01
- Isolated universal 24VDC or 48VDC redundant power inputs
- Wide 110/220 VDC/VAC power supply range
- Modbus/TCP, LLDP, SNMP Inform, QoS, IGMP snooping, VLAN, IEEE 802.1X, HTTPS, SNMPv3, and SSH supported
- -40 to 85°C operating temperature range
Introduction
The PowerTrans PT-508/510 is designed to meet the demands of power substation automation systems (IEC 61850-3, IEEE 1613). The PT-508/510’s optical fiber Fast Ethernet backbone, redundant ring, redundant power inputs (24 VDC or 48 VDC), and isolated power inputs (24 VDC, 48 VDC, or 110/220 VDC/VAC) increase the reliability of your communications and save on cabling/wiring costs. In addition, the DIN-Rail and wallmount design of the PT-508/510 makes network planning easy, and allows greater flexibility by letting you install up to 8/10 Fast Ethernet ports for power distribution applications.
IEC 61850 Substation Solutions
Maximizing a power substation’s availability and safety is the ultimate goal for both transmission grid operators and SAS (Substation Automation System) integrators. A properly optimized SAS ensures safe and continuous operation of substations. This brochure examines some key application scenarios that involve availability and safety, and considers the practical concerns electricity suppliers must account for when planning substation upgrades. In each case the focus is on how Moxa’s communication and computing solutions best minimize error probability, detect errors faster, and speed up fault corrections within the context of IEC 61850.......more
• Technology | |
Standards | IEEE 802.3 for 10BaseT IEEE 802.3u for 100BaseT(X) and 100BaseFX IEEE 802.3x for Flow Control IEEE 802.1D for Spanning Tree Protocol IEEE 802.1w for Rapid Spanning Tree Protocol IEEE 802.1D-2004 for Spanning Tree Protocol IEEE 802.1Q for VLAN Tagging IEEE 802.1p for Class of Service IEEE 802.1X for Authentication IEEE 802.3ad for Port Trunk with LACP IEEE 802.1s for Multiple Spanning Tree Protocol |
• Software Features | |
Management | IPv4/IPv6, SNMPv1/v2c/v3, DHCP Server/Client, DHCP Option 66/67/82, BootP, TFTP, SMTP, RARP, HTTP, HTTPS, Telnet, SNMP Inform, LLDP, Flow Control, Back Pressure Flow Control, Port Mirror, Syslog, RMON |
Filter | IGMPv1/v2, GMRP, GVRP, 802.1Q VLAN, VLAN Unaware, Port-Based VLAN, GVRP |
Redundancy Protocols | STP/RSTP, MSTP, Turbo Ring v1/v2, Turbo Chain, Link Aggregation |
Security | RADIUS, TACACS+, SSL, SSH, Port Lock |
Time Management | SNTP, NTP Server/Client, IEEE 1588v2 PTP (software-based) |
Industrial Protocols | EtherNet/IP, Modbus/TCP |
MIB | MIB-II, Ethernet-like MIB, P-BRIDGE MIB, Q-BRIDGE MIB, Bridge MIB, RSTP MIB, RMON MIB Group 1, 2, 3, 9 |
• Switch Properties | |
Priority Queues | 4 |
Max. Number of VLANs | 64 |
VLAN ID Range | VID 1 to 4094 |
IGMP Groups | 256 |
MAC Table Size | 8 K |
Packet Buffer Size | 1 Mbit |
• Interface | |
RJ45 Ports | 10/100BaseT(X) auto negotiation speed, F/H duplex mode, and auto MDI/MDI-X connection |
Fiber Ports | 100BaseFX ports (SC/ST/LC/MTRJ connector) |
Console Port | RS-232 (RJ45) |
Alarm Contact | 1 relay output with current carrying capacity of 1 A @ 24 VDC |
• Optical Fiber | |
• Power Requirements | |
Input Voltage | • 24 VDC • 48 VDC • 110/220 VDC/VAC |
Operating Voltage | • 18 to 36 V (24 VDC) • 36 to 72 V (48 VDC) • 88 to 300 VDC, 85 to 264 VAC (110/220 VDC/VAC) |
Input Current | (all ports are equipped with fiber)PT-508: • Max. 0.27 A @ 24 VDC • Max. 0.12 A @ 48 VDC • Max. 0.084/0.043 A @ 110/220 VDC • Max. 0.18/0.11 A @ 110/220 VAC PT-510: • Max. 0.39 A @ 24 VDC • Max. 0.18 A @ 48 VDC • Max. 0.10/0.052 A @ 110/220 VDC • Max. 0.234/0.148 A @ 110/220 VAC |
Overload Current Protection | Present |
Connection | 5-pin terminal blocks |
Reverse Polarity Protection | Present |
• Physical Characteristics | |
Housing | Aluminum alloy |
IP Rating | IP40 protection |
Dimensions | 60 x 160 x 110 mm (2.36 x 6.30 x 4.33 in) |
Weight | PT-508: 995 g (2.21 lb) |
Installation | DIN-rail mounting, wall mounting (with optional kit) |
• Environmental Limits | |
Operating Temperature | -40 to 85°C (-40 to 185°F), cold start requires min. of 100 VAC at -40°C |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
• Standards and Certifications | |
Safety | UL 508 |
EMI | FCC Part 15 Subpart B Class A, EN 55032 Class A |
EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kVIEC 61000-4-3 RS: 80 MHz to 1 GHz: PT-508: 20 V/m PT-510: 35 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV IEC 61000-4-5 Surge: Power; 4 kV; Signal: 4 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 IEC 61000-4-11 |
Electrical Substation | IEC 61850-3, IEEE 1613 |
• MTBF (mean time between failures) | |
Time | PT-508: 394,238 hrs PT-510: 372,276 hrs |
Standard | Telcordia SR332 |
• Warranty | |
Warranty Period | 5 years |
Details | www.anhnghison.com |